Invt Che100-0r7g-s2 Manual ((top)) May 2026

The INVT CHE100-0R7G-S2 is a high-performance sensorless vector control drive designed for versatility and efficiency in industrial applications. Whether you are installing a new unit or troubleshooting an existing system, having the technical specifics at your fingertips is essential for maintaining uptime.

This guide serves as a comprehensive overview of the INVT CHE100-0R7G-S2 manual, covering installation, wiring, and key parameter settings. Technical Specifications and Overview

The CHE100 series is known for its compact design and robust torque control. The 0R7G-S2 model is specifically tailored for small-scale machinery. Power Rating: 0.75 kW (1 HP) Input Voltage: Single-phase 220V (S2 designation)

Control Mode: Sensorless Vector Control (SVC) or V/F control Overload Capacity: 150% of rated current for 60 seconds Cooling: Forced air cooling Installation Guidelines

To ensure the longevity of your inverter, proper physical placement is the first step.

Environment: Install in a dust-free, non-corrosive environment.

Orientation: Mount the unit vertically to allow heat to rise naturally.

Clearance: Maintain at least 100mm of space above and below the unit, and 50mm on the sides for airflow.

Temperature: Ensure the ambient temperature stays between -10°C and 40°C. Wiring and Terminals

Refer to the manual's wiring diagram to avoid short circuits or equipment damage. Main Circuit: Connect the single-phase power supply to terminals L and N. Connect the motor leads to U, V, and W. Always connect the PE terminal to a solid ground. Control Circuit:

S1-S4: Programmable digital inputs for forward/reverse or multi-speed steps.

AI1: Analog input (0-10V or 4-20mA) for frequency references. RO1A/RO1C: Relay output for fault signaling or run status. Quick Start Parameter Settings

For most basic applications, you only need to adjust a handful of function codes (P group) to get the motor spinning.

P0.01 (Command Source): Set to 0 for Keypad control or 1 for Terminal control.

P0.03 (Max Frequency): Usually set to 50.00Hz or 60.00Hz depending on your motor. P0.11 (Accel Time): Time in seconds to reach max speed. P0.12 (Decel Time): Time in seconds to reach a full stop. P2.01 (Motor Power): Set to 0.75kW for this specific model. Troubleshooting Common Faults

If the drive trips, the keypad will display an error code. Here are the most common ones found in the CHE100 manual:

OC1/OC2/OC3 (Overcurrent): Check for motor shorts, mechanical jams, or if the acceleration time is too short.

OV1/OV2/OV3 (Overvoltage): Often caused by rapid deceleration. Increase the decel time (P0.12) or add a braking resistor.

UV (Undervoltage): Check the input power supply for drops or loose connections.

OL1/OL2 (Overload): The motor is drawing too much current for too long; check the load and motor settings. Maintenance and Support

Regularly check the cooling fan for dust buildup and ensure terminal screws remain tight, as vibration can loosen them over time. For advanced features like PID control or RS485 communication setups, refer to the full PDF manual provided by INVT.

INVT CHE100-0R7G-S2 Manual: Installation, Wiring, and Troubleshooting Guide

The INVT CHE100 series is a highly efficient sensorless vector control drive designed for high-performance industrial applications. The CHE100-0R7G-S2 model specifically caters to low-power requirements, offering a 0.75kW output with a single-phase 220V input. Whether you are setting up a small conveyor, a fan, or a pump, understanding the technical specifications and programming logic of this inverter is essential for peak performance. Technical Specifications

Before beginning installation, verify that your hardware matches the following electrical ratings: invt che100-0r7g-s2 manual

Model Number: CHE100-0R7G-S2Rated Power: 0.75 kW (1.0 HP)Input Voltage: Single-phase 220V AC (±15%)Output Voltage: Three-phase 0–220V ACRated Current: 4.0AControl Mode: Sensorless Vector Control (SVC) or V/f ControlProtection Rating: IP20 Installation and Environment Guidelines

To ensure the longevity of your INVT drive, the installation environment must meet specific criteria:

Mounting: Always install the unit vertically to allow for natural heat dissipation.Clearance: Maintain at least 100mm of space above and below the unit, and 50mm on the sides.Temperature: Operate between -10°C and +40°C. If the ambient temperature exceeds 40°C, derate the output current by 3% for every additional degree.Moisture and Dust: Avoid direct sunlight, high humidity (above 95% RH), and corrosive gases. Wiring Diagram and Terminals

Proper wiring is the most critical step in preventing drive failure or electrical hazards. Main Circuit Terminals

L, N: Connect your single-phase 220V AC power supply here.U, V, W: Connect these to your three-phase motor. (Note: Never connect input power to these terminals).(+) , (-): DC bus terminals for external braking units (if required).PE: Grounding terminal. Ensure a solid connection to prevent electromagnetic interference (EMI). Control Circuit Terminals

S1 to S4: Multi-function digital inputs (forward, reverse, multi-speed).+10V, AI1, GND: External potentiometer or 0–10V analog input for frequency control.485+, 485-: Standard RS485 communication ports for PLC integration.RO1A, RO1C: Relay output for fault signaling or status monitoring. Basic Programming and Parameter Settings

The CHE100 utilizes a group-based parameter system. To enter programming mode, press the "PRG" key, use the arrows to find the group, and press "DATA/ENT" to modify. Essential Parameters for Startup

P0.01 (Source of Run Command): 0 for Keypad, 1 for Terminal Control, 2 for Communication.P0.03 (Max Output Frequency): Usually set to 50.00Hz or 60.00Hz depending on your motor.P0.11 (Acceleration Time): Time in seconds to reach max frequency.P0.12 (Deceleration Time): Time in seconds to reach a full stop.P2.01 (Motor Rated Power): Set to 0.75kW.P2.02 (Motor Rated Voltage): Set to 220V.P2.05 (Motor Rated Current): Set according to your motor's nameplate (typically around 3.5A–4.0A). Troubleshooting Common Fault Codes

If the drive encounters an error, it will display a fault code on the LED screen.

OC1 / OC2 / OC3 (Overcurrent): Check for a motor short circuit, heavy mechanical load, or if the acceleration time (P0.11) is too short.OV1 / OV2 / OV3 (Overvoltage): Often occurs during rapid deceleration. Increase deceleration time (P0.12) or install a braking resistor.UV (Undervoltage): Check the input power supply for stability or a loose connection.OL1 / OL2 (Overload): The motor or drive is being pushed beyond its current rating. Check for mechanical jams or reduce the load.OH (Overheat): Ensure the cooling fan is running and that there is sufficient airflow around the heat sink. Safety Precautions

High Voltage Warning: After powering off the drive, wait at least 5 minutes for the DC bus capacitors to discharge before touching any terminals.No Capacitors: Never connect capacitors or surge absorbers to the output (U, V, W) terminals.Phase Insulation: Before connecting the motor, use a megohmmeter to ensure the motor phase-to-ground insulation is intact.

By following this manual guide, you can ensure a stable and efficient setup for your INVT CHE100-0R7G-S2. For complex automation logic or Modbus communication setups, refer to the full manufacturer PDF for advanced parameter mapping.

The model number "0R7G-S2" breaks down its primary capabilities: Rated Power : 0.75 kW (4.5 A output current). Input Voltage : Single-phase (1AC) 220V ± 15%. Output Frequency Range : 0 to 400 Hz. Control Modes

: Sensorless Vector Control (SVC), V/f control, and torque control. Key Features & Functionality According to the official product description from INVT , this unit is optimized for: High Performance at Low Frequency : Provides a starting torque of 150% at 0.5 Hz. Multi-Step Speed Control : Supports up to 8 programmable speed stages. Built-in Protection

: Includes up to 25 fault protection mechanisms, including overcurrent, overvoltage, undervoltage, and overheating. Connectivity

: Features an RS-485 communication interface with standard Modbus protocol.

: Units from 0.4 kW to 11 kW have built-in braking units to facilitate quick stops. Operational Safety and Installation emphasizes several critical safety protocols: Qualified Personnel

: Installation and maintenance must be performed only by qualified electricians. Discharge Time

: Wait at least 5 minutes after power-off before opening the cover to ensure internal capacitors have discharged.

: Ensure the grounding terminal is properly connected to prevent electrical shock. Common Applications This inverter is widely used in: Production Machinery

: Woodworking hand tools and furniture production (e.g., KDT edge banding machines). : Fans and pumps requiring precise speed control. Automation

: Applications requiring rapid torque response and high speed accuracy.

: The CHE100 series has been officially discontinued by INVT and is typically replaced by newer models like the 1. Basic Specifications (Model breakdown)

. You can still find documentation and technical support files on the INVT Download Center parameter settings for a particular machine application, or do you need the wiring diagram for this model?

Частотный преобразователь INVT CHE100-0R7G-S2

The INVT CHE100-0R7G-S2 is a general-purpose frequency inverter from the CHE100 series, designed for sensorless vector control and V/f control. The manual for this specific 0.75kW single-phase model provides comprehensive guidance on installation, wiring, and parameter configuration to optimize performance in applications like pumps, fans, and high-speed control systems. Key Technical Specifications

Power Rating: 0.75 kW (G-type for constant torque/general purpose). Input Voltage: Single-phase 220V AC ±15%. Input Frequency: 47~63 Hz. Output Current: Rated up to 4.5 A. Output Frequency Range: 0 ~ 400 Hz.

Control Modes: Sensorless Vector Control (SVC), V/f control, and torque control. Critical Parameter Settings

The manual highlights several essential parameters for initial setup and tuning:

Factory Reset: Set P0.13 to 1 to restore factory default settings.

Control Mode (P0.00): Set to 0 for sensorless vector control. Frequency Limits: P0.03: Maximum frequency (default 50/60Hz). P0.04: Upper frequency limit. P0.05: Lower frequency limit. Acceleration/Deceleration: P0.08: Acceleration time. P0.09: Deceleration time.

Motor Autotuning (P0.12): Setting this to 1 initiates dynamic autotuning. Press the RUN button on the keypad; the display will show "END" once finished. Wiring and Terminal Functions CHF100A Manual.pdf - INVT

See Group PC parameter settings. 9.2 Communication Modes. 9.2.1 The protocol is Modbus protocol. Besides the common register Read/ CHE100 Inverter User Manual PDF - Scribd

Settle the abnormality. No. Achieve the required control. Yes. End. Motor parameter. autotuning (set P0.12) Output frequency. Max.

Частотный преобразователь INVT CHE100-0R7G-S2

The INVT CHE100-0R7G-S2 Go to product viewer dialog for this item.

is a compact, high-performance open-loop vector control inverter (Variable Frequency Drive) designed for small power applications, typically 0.75kW (1HP), 220V single-phase input/three-phase output [1, 2].

Here is a structured summary of the manual content for this unit: 1. Technical Specifications Model: CHE100-0R7G-S2 Power Rating: 0.75 kW (1 HP) Input Voltage: Single-phase 200–240V ( Output Voltage: Three-phase 0–240V

Control Mode: Open-loop vector control (SVC) and V/F control.

Overload Capacity: 150% rated current for 60 seconds (G type). 2. Wiring and Installation Input Terminals: R, T (Single-phase power input). Output Terminals: U, V, W (To 3-phase AC Motor).

Control Terminals: Includes analog inputs (AI), digital inputs (DI), and relay outputs (NO/NC).

Wiring Precautions: Ensure correct voltage, separate power cables from control signal cables to avoid interference, and ensure proper grounding. 3. Keypad Operation

LED Display: Shows running status, frequency, speed, voltage, or parameters.

Function Keys: PRG/ESC (Enter/Exit menu), DATA/ENT (Confirm), RUN/STOP (Start/Stop), UP/DOWN (Parameter change/Frequency adjust). 4. Basic Function Parameter Settings P0.01: Control Mode ( P0.03: Max Frequency ( P0.04: Upper Frequency Limit. P0.07: Command Source ( : Terminal, : Communication). P0.11/P0.12: Acceleration/Deceleration time. P0.15: Terminal Jog. P1.00: Motor Rated Power. P1.01: Motor Rated Frequency. 5. Troubleshooting (Fault Codes)

OU1/OU2/OU3: Overvoltage (During accel/decel/constant speed). LU: Undervoltage. OC1/OC2/OC3: Overcurrent. OL1/OL2: Overload (Motor or Inverter). EF: External fault.

Disclaimer: This information is a summary based on typical INVT CHE100 documentation. For installation, always consult the official INVT documentation to ensure safety and accuracy. factory default typically 4 kHz)

To get the specific wiring diagram or parameter for your application, tell me:

What type of machine is this driving (e.g., pump, fan, conveyor)? Are you using keypad control or external switches?

The INVT CHE100-0R7G-S2 Go to product viewer dialog for this item.

is a compact, high-performance frequency inverter (VFD) designed for sensorless vector control. It is primarily used in light industrial applications where precise motor control and energy efficiency are required. 📋 Key Technical Specifications

The model number contains critical information about its capabilities: Input Voltage: 1-Phase 220V ±15% Output Power: 0.75kW (approx. 1 HP) Frequency Range: 0Hz to 400Hz

Control Modes: Sensorless Vector Control (SVC) and V/f control

Inputs: 4 programmable digital inputs and 2 analog inputs (0-10V/4-20mA) 🛠️ Core Features

High Start Torque: Provides 150% torque at 0.5Hz, making it ideal for heavy-start loads.

Safety Protections: Includes 25 different fault protections, such as overcurrent, overvoltage, and overload.

Speed Response: Features rapid torque response and high speed control accuracy.

Energy Efficiency: Optimized for Pump & Fan applications to reduce power consumption. 📖 Installation & Setup Essentials

The Official Operation Manual highlights several critical setup procedures:

Environment: Must be installed in a well-ventilated area with a temperature range of -10°C to 40°C.

Wiring: Use the standard typical wiring diagram (found in Section 4.3 of the manual) to connect main circuit terminals.

Keypad Operation: The unit features a small external keypad for parameter setting and monitoring.

Fault Diagnosis: Refer to the "Fault diagnosis and solutions" section if the keypad displays error codes like "OC" (Overcurrent) or "OV" (Overvoltage). 🔗 Manual Downloads

You can find the full documentation on these reputable platforms: ManualsLib - Operation Manual (124 pages) INVT Official Download Center Scribd - CHE100 User Manual PDF

💡 Pro Tip: Always ensure the unit is powered off for at least 5 minutes before performing maintenance to allow DC bus capacitors to discharge.

It seems you’re looking for a feature (or a list of features) of the inverter model INVT CHE100-0R7G-S2, likely from its manual.

Based on the INVT CHE100 series manual (often titled CHE100 Series High-performance Vector Control Inverter), here are the key features for that specific model (0.75kW, 220V single-phase input):

3. I/O & Interface Features

Chapter 1: Model Breakdown – Understanding “CHE100-0R7G-S2”

Before diving into the manual, let’s decode the model number, as the manual refers to these specifications constantly:

| Code Section | Meaning | Interpretation | | :--- | :--- | :--- | | CHE100 | Product Series | INVT’s basic vector control VFD series | | 0R7 | Power Rating | 0.75 kW (approx. 1 HP) | | G | General Purpose | Suitable for constant torque loads (conveyors, mixers) | | S2 | Input Voltage | Single-phase, 200V–240V AC input (output is 3-phase) |

Critical Note from the Manual: The output of the CHE100-0R7G-S2 is three-phase 220V. It is designed to control a three-phase induction motor, not a single-phase motor. Attempting to run a single-phase motor without derating will damage the drive.


Mistake #4: Misinterpreting "Active High" vs "Active Low"

The control terminal logic (PNP vs NPN) is explained in the manual. Connecting a PLC output incorrectly can damage the drive’s 24V internal supply.


2. Control & Performance Features

1. Basic Specifications (Model breakdown)